An STC rating, short for sound transmission class, is a single number for how well a wall, floor, ceiling, window or door blocks airborne sound such as voices and television, measured in a laboratory. Higher is better. A plain wood-stud wall rates around 35; the building code for apartments asks for 50.
The same number appears on drywall assemblies, replacement windows, acoustic doors and wall air conditioners, and this page covers how it is worked out, what it leaves out, and how it differs from the ratings printed beside it.
What does an STC rating mean?
STC is the laboratory rating for airborne sound insulation. ASTM E90 measures how much sound a specimen stops between two test rooms, and ASTM E413 turns those measurements into one number, which E90 calls the sound transmission class.
E90 covers "walls of all kinds, operable partitions, floor-ceiling assemblies, doors, windows, roofs, panels, and other space-dividing elements." The laboratory is built so that the specimen is the only significant path between the rooms.
E413 is specific about what the rating is good for. Its ratings "correlate in a general way with subjective impressions of sound transmission for speech, radio, television, and similar sources of noise in offices and buildings." For other sources, the standard says the method is not appropriate, a limit covered in the low-frequency section below.
How is STC calculated?
By fitting a standard curve to the test results. According to the Federal Highway Administration's description, the lab measures transmission loss "in 16 one-third octave bands" between 125 Hz and 4000 Hz and compares them with a reference contour.
The contour is slid up the chart as far as it will go while two limits hold:
- the deficiencies, where the measured loss falls below the curve, add up to no more than 32 dB
- no single band falls more than 8 dB below the curve
The STC is the value of the curve at 500 Hz. A 1970 National Bureau of Standards report for the federal housing program described the same steps, then drawn from ASTM E90-66, and explained their purpose: to make it less likely that a rating rests on the transmission loss at one particular frequency.
What can you hear through a wall at each STC rating?
The best-sourced scale comes from Canadian housing research. A Canada Mortgage and Housing Corporation guide from 2005 reproduces this table from Warnock, Quirt and Lio, researchers at the National Research Council of Canada, first published by CMHC in 2002.
| Wall STC | What comes through, in the CMHC table's words |
|---|---|
| 45 | "Loud or amplified speech audible"; "Loud music audible, and bass notes particularly strong" |
| 50 | "Loud or amplified speech faintly audible"; "Loud music barely audible, but bass notes quite noticeable" |
| 55 | "Loud music not generally audible, but bass notes still heard" |
| 60 | "Loud music inaudible except for very strong bass notes" |
The table starts at 45. Charts that describe STC 25, 30 and 35 walls circulate widely, but we did not find one in a primary source we could open, so they are left out here.
Bass outlasts speech at every step, and even at STC 60 the table expects strong bass notes to get through, the first hint that the rating weighs low frequencies lightly.
For windows, Andersen publishes a shorter scale of its own:
| Window STC | Andersen's description |
|---|---|
| <30 | "You'd be able to hear and understand a loud conversation happening outside." |
| 30 to 35 | "You might hear a loud, outdoor conversation but wouldn't be able to make out the words." |
| 36 to 40 | "Even loud conversations are hardly audible." |
Building codes set STC 50 between homes
Section 1206.2 of the 2021 International Building Code covers walls, partitions and floor-ceiling assemblies separating dwelling units and sleeping units from each other or from public or service areas. They must have "a sound transmission class of not less than 50 where tested in accordance with ASTM E90." Tested in the finished building under ASTM E336, the target is a normalized noise isolation class, NNIC, of at least 45.
Openings for pipes, electrical boxes, recessed cabinets, bathtubs and ducts must be sealed or treated to keep the rating. The requirement "shall not apply to entrance doors," though the code adds that such doors "shall be tight fitting to the frame and sill."
Canada's model code followed a similar path. National Research Council Canada notes that the 1990 National Building Code raised the STC between dwelling units from 45 to 50. The 2005 CMHC guide lists that code's 50, and 55 next to elevator shafts, beside its own best-practice figures of 55 and 65.
Older U.S. guidance aimed higher. The 1970 NBS report quotes three grades from a Federal Housing Administration guide: STC 55, 52 and 48 for walls between dwelling units, with emphasis on the middle grade.
Shared walls are only part of an apartment's noise, and our quiet apartment guide looks at which household machines reach the neighbors through floors and walls.
STC ratings for common wall assemblies
Construction matters more than wall thickness. These ratings come from Johns Manville's 2019 reference guide, which credits NAIMA, the insulation makers' association, for the data. All use 2x4 studs at 16 inches on center and 1/2 inch gypsum board.
| Wall construction | Cavity | STC |
|---|---|---|
| Single studs, 1 layer per side | Empty | 35 |
| Single studs, 1 layer per side | R-13 fiberglass batts | 38 |
| Single studs, 2 layers per side | R-13 batts | 45 |
| Single studs, 1 layer per side, resilient channels | R-13 batts | 47 |
| Staggered studs, 1 layer per side | Empty | 36 |
| Staggered studs, 1 layer per side | R-13 batts | 49 |
| Double studs, 1 layer per side | Empty | 46 |
| Double studs, 1 layer per side | R-13 batts | 56 |
The jumps follow a pattern that National Research Council Canada found after testing more than 250 gypsum board walls. The two faces need to be isolated from each other, by staggered or double studs or resilient channels. Without that, insulation does little: batts add 3 points to the single-stud wall above, but 13 to the staggered wall and 10 to the double wall. In NRC's words, absorptive fill in a rigidly connected wall "is a waste of money."
Mass and depth help once the faces are isolated. In one series of steel-stud walls, doubling the weight of gypsum board raised the STC by about 10 points. Doubling the depth of a fully insulated cavity also added about 10. NRC also found that an extra board inside a double-stud wall lowered it from STC 58 to 55.
What STC rating do windows have?
Usually between 25 and 40. The CMHC guide gives that range, depending on "type, glazing, frame, size of air space and how they open." It recommends STC 35 to 40 near arterial roads, factories and airports, and says specialty acoustic windows reach STC 45 to 55.
Andersen puts a typical dual-pane window lower, at STC 25 to 30. For more quiet it suggests the 30 to 35 range, naming a 100 Series window with its STC upgrade or a 400 Series window with laminated glass, which it describes as "glass-vinyl-glass."
Set those numbers beside the wall. A window of STC 30 in a wall of STC 50 is the easier path for sound, and the FHWA manual treats any wall with a window or door as a composite whose rating "must be determined" from both parts.
A window air conditioner sits in that same opening. Our window AC guide and the quiet bedroom guide deal with the noise those machines make inside the room, a separate problem from what the window lets in.
STC ratings for doors
Standard doors rate low. The CMHC guide puts them at STC 27 to 32 and says better seals around the door can add up to 5. Purpose-built sound control doors are "much heavier than conventional doors" and can exceed STC 50, with frames and hinges built for the weight. Seals raise a second question in apartment buildings. Many corridors are pressurized so that air flows under suite doors into each unit, and the CMHC guide advises checking with building management before closing that gap, since it can affect fire safety and ventilation.
Why does STC miss bass and traffic noise?
Because its test range stops at 125 Hz and its curve was shaped around speech. ASTM E413 lists sources the rating does not suit, among them machinery, power transformers, musical instruments, many music systems, and motor vehicles, aircraft and trains. For those, the standard says "accurate assessment of sound transmission requires a detailed analysis in frequency bands."
Its answer for building facades is OITC, the outdoor-indoor transmission class in ASTM E1332. OITC uses data from 80 to 4000 Hz and a source spectrum that averages aircraft takeoff, road traffic and a diesel locomotive. The standard notes that the spectrum's "strong low-frequency content" means a product earning a high OITC "must have strong low-frequency transmission loss."
Andersen's window page draws the line simply: STC focuses on sound within a building, while OITC focuses on sound coming into it, "think cars, airplanes and construction noise."
The two can differ by a wide margin. In GE's Zoneline product guide, the PTAC, a heat and cool unit installed through an exterior wall, rates STC 29 and OITC 20 from third-party tests in 2015. Our PTAC guide notes that GE prints these blocking ratings but no operating sound level, and the through-the-wall AC guide covers the sleeve units that fill the same kind of hole.
STC vs IIC for floors
STC covers airborne sound through a floor; IIC, impact insulation class, covers footsteps and dropped objects. The 2021 IBC asks floor-ceiling assemblies between dwellings for both: STC 50 and IIC 50 in the lab, or NNIC 45 and NISR 45 in the field.
IIC is measured with a standard tapping machine, and ASTM E989 states that the rating strictly applies only to that machine. It "does not deal with low frequency sounds below 100 Hz" from people walking on lightweight joist floors, nor with squeaks and rattles.
A floor good at one can be poor at the other. The CMHC guide warns that construction "with a good STC rating for airborne sound will not necessarily provide acoustic privacy for impact sound," and recommends IIC 55 for bare floors and 65 for carpeted ones. Concrete topping on a wood subfloor, its example, cuts airborne sound but lets impact sound through readily unless a cushioning layer sits between them.
STC vs NRC
STC measures blocking; NRC, the noise reduction coefficient, measures absorption inside a room. ROCKWOOL defines NRC as the average of a material's absorption coefficients "at frequencies of 250, 500, 1,000, and 2,000 Hz, rounded to the nearest .05," tested to ASTM C423 in a reverberation room.
The scale runs from 0.00 to 1.00, and ROCKWOOL treats a material above 0.70 as sound absorbing. Its shorthand: "ceilings are most effective at absorbing noise; walls are best at blocking noise." A ceiling panel's NRC says how much sound it soaks up in the room it faces; a wall's STC says how much passes through to the next room. Neither number predicts the other.
Is STC the same as decibels?
No. STC has no unit; it is a class number read off a fitted curve. The measurements underneath it are transmission loss, which the 1970 NBS report defines as "the number of decibels by which sound energy incident on one side of a partition is reduced in transmission through it." A wall rated STC 50 does not take 50 decibels off every sound. The curve is pinned at 500 Hz, and the loss at low frequencies is usually smaller, which is the pattern in the CMHC table's bass notes.
The NBS report gives a worked example in decibels. Outdoor levels of 80 to 90 dB(A) in congested urban areas, against a daytime indoor criterion of NC-40, about 50 dB(A), call for a shell that cuts roughly 30 to 40 dB; "as a rough rule-of-thumb," it suggests STC 35 or better.
For what those dB(A) figures mean, see our dBA explainer and decibel chart. STC describes the barrier rather than the noise source, much as sound power and sound pressure separate a machine from what reaches a listener.
STC vs Rw
Rw, the weighted sound reduction index, is the international counterpart from ISO 717-1. ASTM E413 notes that the ISO method uses 100 to 3150 Hz and sets no maximum deficiency at any single frequency, and that "for most partitions, the two ratings differ by only one or two points."
Why a wall rated STC 50 can perform worse in the building
The lab rating is a ceiling. In buildings, sound also travels around a wall through floors, ceilings and junctions, called flanking, and ASTM E90 says lab ratings "represent an upper limit to what would be measured in a field test." E413 adds that construction errors can lower the field result.
Field tests under ASTM E336 report apparent STC (ASTC) or NNIC instead. National Research Council Canada's 2006 wood-frame guide states that sound isolation between rooms "is systematically less" than the STC of the separating wall or floor. In one floor series it tested, even a single flanking wall left the apparent STC 1 or 2 points below the direct figure.
Standards and documents behind this page
The definition and calculation come from the ASTM summary pages for E90, E413, E336, E1332, E989 and C423, and from the FHWA's building insulation manual. Code figures come from the 2021 International Building Code on the ICC's site. Older U.S. criteria come from the 1970 NBS report. The hearing scale, door and window ranges and Canadian code figures come from CMHC's 2005 apartment guide; wall research comes from two National Research Council Canada publications. Product ratings are quoted from Johns Manville, Andersen, GE and ROCKWOOL documents as published. We did not measure any wall, window or door.