Most standby spec sheets give two sound levels, one for the weekly self-test and one for running through an outage.
During exercise the generator starts, runs a few minutes and shuts down, usually at a lower engine speed. Generac calls this Quiet-Test low-speed exercise mode, Briggs & Stratton calls it Low Idle Mode, and Kohler calls it engine exercise. Neighbors hear it on an ordinary afternoon, week after week.
The running figure is the outage, and here the makers part ways on the condition. Generac and Cummins say "at normal load". Briggs & Stratton says normal operation "based on average household usage". Kohler says "full-speed generator diagnostics and normal operation", adding "with no load" on three spec sheets, and Champion gives one "Operational Volume" with no condition at all.
An exercise figure never ranks against a running one here. They describe different engine speeds, and the gap is large: 49 to 61 dB(A) on Generac's 10 kW model.
Our Generac generator decibels page lists every current Generac standby model the same way, exercise against exercise and running against running, with the liquid-cooled Protector series kept apart.
Same distance, different microphone positions
Every figure in this guide is at 7 meters, a shared distance that is rare in any category and useful. The makers stand the microphone in different places, though.
| Maker | Where the figure is taken, in its words |
|---|
| Generac | Front of the unit; "Sound levels taken from other sides of the generator may be higher depending on installation parameters." |
| Kohler | "Lowest of 8 points measured around the generator" on most models |
| Briggs & Stratton | "Per ISO 3744", at the "lowest microphone at 7m" |
| Cummins | "Quietest point at a normal load." |
| Champion | "measured at 23 ft. (7 m)", nothing more |
Kohler's 10RESV sheet shows what the choice of point does, giving both versions: an 8-point average of 67 dB(A) in exercise, and 64 at the quietest point.
A lowest-point figure is the most flattering number a maker can quote. A front figure may or may not be. A few decibels between a Generac figure and a Kohler one is therefore unknown territory, for the reasons set out in comparing decibel ratings from different makers.
What is the quietest home standby generator during its weekly test?
The Generac 10 kW model 7257, at 49 dB(A) in Quiet-Test, measured from the front. Every figure below is at 7 meters, in the mode each maker uses.
| Exercise figure | Generators, with how each was measured |
|---|
| 49 dB(A) | Generac 10 kW model 7257, Quiet-Test, front |
| 52 dB(A) | Kohler 24RCLA and 38RCLC, liquid-cooled, lowest of 8 points, no load |
| 55 dB(A) | Generac's newer 14, 18, 22, 24, 26 and 28 kW models, and the Guardian 14 and 18 kW |
| 56 dB(A) | Kohler 26RCA, lowest of 8 points |
| 57 dB(A) | Generac Guardian 10, 22, 24 and 26 kW |
| 62 dB(A) | Briggs & Stratton PowerProtect+ 18kW and 22kW and both DX models, lowest microphone |
| 63 dB(A) | Briggs & Stratton PowerProtect 26kW, and Kohler 14RCA |
| 64 dB(A) | Briggs & Stratton PowerProtect 22kW |
| 65 dB(A) | Briggs & Stratton PowerProtect 13kW |
| 66 and 67 dB(A) | Kohler 20RCA, and the 10RESV as an 8-point average |
Top to bottom, the spread is 18 dB(A). On the usual rule of thumb that 10 dB sounds about twice as loud, that is a large difference, bigger than any plausible gap in method. Our decibel chart puts these levels beside everyday sounds.
How loud is a whole house generator running in an outage?
From 61 to 67 dB(A) on Generac's sheets, at 7 meters and normal load. Other makers state other conditions, so the running figures sit in groups rather than one ranking.
| Condition at 7 m | Running figures |
|---|
| Normal load | Generac 10 kW models 61 dB(A); Generac 14 and 18 kW and Cummins RS13A, RS17A and RS20A 65; Generac EcoGen 15 kW 66; Generac 22 to 28 kW 67 |
| Average household usage, lowest microphone | Briggs & Stratton PowerProtect 26kW 65; PowerProtect+ range 66; PowerProtect 22kW 68; 13kW 69 |
| Kohler full speed or normal operation, lowest point | 24RCLA and 38RCLC 60 at no load; 26RCA 67; 14RCA 69; 20RCA 70 |
| Kohler 8-point average, no load | 10RESV 71 |
| No condition stated | Champion 14 kW aXis 62; 22 kW aXis 67; 26 kW fleX 68 |
A Kohler figure at no load is not a figure at normal load, and Champion's 62 could describe either, so no ranking crosses these rows.
Champion's smaller standby units publish figures too. Our Champion generator decibels page shows the 8.5 kW Select Circuit 100177 as the quietest Champion standby unit, 59.5 dB(A) from 23 ft (7 m), again with no load stated.
Kohler's pages and spec sheets disagree on four models
Of the six Kohler models checked, four have product pages and spec sheets that give different numbers. Wherever they disagree, this guide quotes the sheet, because it states the distance and the method.
The 24RCLA page says 54 dB(A) in exercise and 61 at full speed; the sheet says 52 and 60, and the same page's feature text also says 52. On the 38RCLC, the page says 54 and 62 against the sheet's 52 and 60. The 14RCA page gives 67 at full speed and the sheet 69. The 20RCA page gives 64 and 69, while its sheet gives 66 and 70 and calls them both an average and the lowest of 8 points. Only the 26RCA matched, one reason it is the Kohler air-cooled pick.
Those same pages say of the 26RCA that "No air-cooled generator is quieter". On exercise figures, Generac's air-cooled units list 49 and 55 against Kohler's 56. The methods differ, so neither claim settles it. Still, the published figures do not back the slogan.
Is there a noise limit for home standby generators?
There is no federal limit. Your local noise ordinance decides, and a code officer checks it at your property line, not at the 7 meters on a spec sheet.
Montgomery County, Maryland, is a useful example because its Department of Environmental Protection writes about standby generators directly. Standby generators, which can operate on a 24-hour basis, "are required to meet Montgomery County's more restrictive nighttime standard of 55 dBA" at the nearest receiving residential property line. The county's advice is to "Purchase the quietest generator available", to choose the location to minimize noise for neighbors, and to "Schedule the recommended periodic testing of generators to occur at times when building occupants and nearby neighbors are least likely to be disturbed." Compliance, it adds, is the property owner's responsibility.
It also offers a rule of thumb: each doubling of distance from a point source brings about a 6 dBA drop. That is the county's estimate, not a maker figure, and none of the figures above has been converted with it.
Other counties and cities set different numbers and hours, and treat generators running during an outage differently. Read the code itself, or ask your permitting office, before you choose a spot for the pad. Our yard noise overview covers the other outdoor machines that count toward what neighbors hear.
Placement has a safety side as well. Generac's spec sheets say its units can go "as close as 18 in (457 mm)" to a structure, but "Must be located away from doors, windows, and fresh air intakes and in accordance with local codes."
The quietest exercise is a controller setting
Ask the installer for the quietest mode and a time of day the neighbors will not mind. The exercise is what they hear most, so its settings count as much as the figure on the sheet, and changing them costs nothing.
Generac's newer controller offers exercise weekly, bi-weekly or monthly, for 5 to 20 minutes, with a low-speed option. Its Smart Exercise skips a scheduled test if the generator ran for more than 5 consecutive minutes in the prior 72 hours. Kohler offers a 90-second eco-exercise on the 26RCA, and Cummins describes a crank-only exercise that runs diagnostics without starting the engine.
Is a liquid-cooled generator quieter than an air-cooled one?
Within Kohler's range, yes. Three of its five liquid-cooled units, the 24RCLA, 30RCLA and 38RCLC, list the lowest Kohler figures, 52 dB(A) in exercise and 60 running at no load, against 56 and 67 for the air-cooled 26RCA. They run at 1,800 rpm, weigh well over 1,000 lb shipped, and start at $17,900 and $22,949 MSRP. Every current Kohler model is charted on our Kohler generator decibels page.
Most homes get an air-cooled generator, which runs at 3,600 rpm, and Generac's air-cooled 10 kW lists a lower exercise figure than any Kohler, measured a different way.
For a lower running figure, sizing does more than cooling. Across Generac's range, a 10 kW unit runs at 61 and every model from 22 kW up runs at 67, so a smaller air-cooled unit sized to the house is the better route for most buyers.
Champion, Cummins and Briggs & Stratton publish less
Each leaves something out, and so does Generac's EcoGen. Champion gives an Operational Volume at 23 feet with no load or mode. Cummins gives a normal-load figure but no exercise figure, on a spec sheet dated 2019, and cummins.com refused our requests, so neither a current page nor a price could be checked.
The EcoGen 15 kW has a 66 dB(A) normal-load figure but no Quiet-Test figure, and its sheet says it is designed for use with alternative energy and storage. No PowerPact model appears in Generac's current standby listing. Briggs & Stratton's product pages list "Normal Operating Sound" with no distance; the distance and the ISO 3744 method are in its spec sheets.