Mini split making noise when off? Clicks, cracks and gurgles

Written by · Checked against 7 sources
· 16 min read

Illustration of a wall-mounted mini-split indoor unit with its louver open above a window

A mini split making noise is usually refrigerant, condensate or plastic flexing. What Mitsubishi Electric, LG, Gree and MRCOOL call normal, and when to switch off.

Key takeaways

  • LG says a relay in its wall units can switch on about every two hours to preheat the outdoor unit, which explains a click or clunk from a head that is switched off.
  • Mitsubishi Electric traces a burble in the drain hose to a range hood or ventilation fan pulling outside air up the hose, and lists it among normal sounds.
  • During defrost the indoor fan stops: Pioneer gives 2 to 10 minutes, Mitsubishi Electric says it ends within 10, MRCOOL heads show DF and Fujitsu flashes the OPERATION lamp.
  • Of the 98 ductless systems in our catalog on October 26, 2026, 22 say their indoor figures come from an anechoic chamber or room, and 8 record a microphone distance.
On this page
  1. Is it normal for a mini split to make noise?
  2. Why is my mini split making a clicking noise?
  3. Why is my mini split making cracking or popping noises?
  4. Why is my mini split making a gurgling noise?
  5. Why does my mini split sound like water dripping?
  6. Why is my mini split hissing?
  7. Why is my mini split making noise when off?
  8. Why does my mini split beep or buzz?
  9. What does a mini split do indoors during defrost?
  10. Why is my mini split rattling or humming?
  11. Which mini split noises mean you should switch it off?
  12. How loud is a normal mini split indoor unit?
  13. How do mini split makers measure indoor unit noise?
  14. How did we put this page together?
  15. What makers publish
  16. FAQs
  17. How we reviewed this article

A mini split making noise from its indoor head is usually doing something its maker planned for: moving refrigerant, draining condensate, flexing a plastic panel as it warms or cools, resetting a louver, or pausing for a defrost cycle. Clicks, cracks, gurgles, a soft hiss and dripping after shutdown all sit on the manuals' lists of expected sounds.

The sounds the makers treat as trouble are a smaller group: rattling from the fan, water leaking out of the head, a buzzer that will not stop, and any sound the manual calls loud or abnormal.

This page covers the wall-mounted indoor unit and what the remote and display do while it makes noise. Outdoor unit noise and winter defrost sounds outside the house are in our heat pump noise explainer. Every explanation below is quoted from Mitsubishi Electric, LG, Gree, MRCOOL, Pioneer, Senville and Fujitsu documents.

Sound from the indoor headWhen you hear itWhat the makers sayNormal?
Click or clunkIdle, or switched offRelay, fan or compressor switchingYes (LG, Mitsubishi Electric)
Crack, pop, squeakStart, stop, after heatingPlastic panels expanding and shrinkingYes (Mitsubishi Electric, Gree, LG, MRCOOL)
Burble or gurgleKitchen fan on, or windy dayAir pulled up the drain hoseYes (Mitsubishi Electric)
Running water, trickleOn, off, just after eitherRefrigerant or condensate flowingYes (Gree, LG, Mitsubishi Electric)
DrippingJust after switching offCondensate in a concealed drain hoseYes (LG)
Silence, no warm airHeating, in cold weatherOutdoor unit defrostingYes (Pioneer, Mitsubishi Electric, Fujitsu)
Rattle or tappingFan runningFan touching the housingNo, needs service (LG)

Is it normal for a mini split to make noise?

Yes. Mitsubishi Electric, Gree, MRCOOL, Pioneer and Senville each print a table of indoor unit sounds that are not faults, and LG publishes a support page sorting normal sounds from the ones that need service.

The overlap between those tables is large. Most of what an owner hears comes from four sources: refrigerant changing speed or direction in the pipes, condensate on its way to the drain, plastic parts reacting to temperature, and small motors for the louver and fan starting or stopping.

A quiet room makes all of it easier to hear. A modern head can run below 20 dB(A) on its lowest fan speed, so a tick from the front panel that would vanish under a window unit's fan stands out at 2 a.m.

Why is my mini split making a clicking noise?

Clicking from a mini split's indoor head usually comes from a relay or a motor switching on or off. LG and Mitsubishi Electric both describe this as a normal operating sound, and neither gives the owner anything to fix.

LG's help library names a part most owners never think about. On wall-mounted units, it says, "This relay may turn on every two hours to preheat the outdoor unit, making a normal clicking or clunking sound."

Mitsubishi Electric's MSZ-GL operating instructions list "Mechanical sound is heard from the indoor unit" and explain it as "the switching sound in turning off/on the fan or the compressor." That manual is the New Zealand edition; North American models have their own manuals, which may word this differently.

Can the louver make a clicking or rushing sound?

Yes. MRCOOL's manual says "A rushing air sound may occur when the louver resets its position." MRCOOL also tells owners not to move the louver by hand; to reset it, the owner turns the unit off and disconnects the power.

Mitsubishi Electric explains two louver moves that can sound like the unit acting up. In COOL or DRY mode, after half an hour to an hour of air blowing downward, the vane goes horizontal "to prevent water from condensing and dripping." In heating, it also goes horizontal during defrost or when the air coming out is too cool.

Why is my mini split making cracking or popping noises?

Cracking from a mini split is plastic moving as it warms or cools. Mitsubishi Electric, Gree, LG and MRCOOL all list it as normal, typically just after the unit starts, stops or finishes a spell of heating.

Mitsubishi Electric's table says a cracking sound "is generated by the expansion/contraction of the front panel, etc. due to change in temperature." Gree's Livo owner's manual pins the cracking to a unit "turned on or turned off just now" and calls it the sound of "friction caused by expansion" of the panel or other parts as the temperature changes.

LG puts it the same way: "You may hear a snapping or popping sound as internal plastic components react to temperature changes." MRCOOL says a squeak "may occur after running the unit in heat mode due to expansion and contraction of the unit's plastic parts."

Why does it crack during a self-clean cycle?

Self-clean swings the coil between cold and warm on purpose, so plastic moves more than usual.

Pioneer warns its 30 minute Self-Clean "can cause uncommon noises from the machine" and adds: "These noises are normal, resulting from plastic parts expanding and contracting due to temperature changes."

MRCOOL's and Senville's Active Clean freezes moisture on the indoor coil, thaws it fast, then blows the coil dry with warm air before switching itself off after 20 to 45 minutes. Senville's manual says that while it works, "A “pi-pi” sound will be heard." Gree warns its auto clean may bring "some noise," from flowing liquid and parts expanding or shrinking.

Why is my mini split making a gurgling noise?

A gurgle from a mini split usually comes from the condensate drain hose or from refrigerant in the indoor coil. Mitsubishi Electric traces one burbling sound to a range hood or ventilation fan pulling outside air up the drain hose.

Mitsubishi's table lists a "Burbling" sound and says: "This sound is heard when the outside air is absorbed from the drain hose by turning on the range hood or the ventilation fan, making water flowing in the drain hose to spout out." It adds that strong wind blowing into the end of the hose does the same.

That makes a gurgle that lines up with the cooker hood or an extractor fan a matter of air in the hose, not a refrigerant problem. Mitsubishi offers no fix in the table; it lists the sound among normal ones. A drain hose that is kinked, blocked or not draining is a job for the installer.

The other gurgle is refrigerant. LG says "You may hear hissing, gurgling, or trickling as refrigerant moves through the indoor unit." On ceiling cassettes, which pump their condensate up and out, LG also expects "a gurgling or motor sound when the pump operates, especially in a quiet room."

Why does my mini split sound like water dripping?

Dripping you hear but cannot see is condensate draining out of the head, and LG calls it normal just after switch-off. Water you can see coming from the head is different: three makers say to stop using the unit.

LG says "You may hear a normal dripping sound from the indoor unit shortly after turning off your air conditioner." The sound often comes from the bend in a drain hose hidden in the wall, and LG's advice is: "To reduce this sound, extend the drain hose." Where the hose runs down the outside wall, wind can knock it about; LG says to fix it to the wall.

Mitsubishi Electric explains a running water sound as "the sound of refrigerant or condensed water flowing in the unit." Gree says a "water flowing" noise after the unit has just been switched on or off is refrigerant, "which is a normal phenomenon."

What if water is actually leaking from the indoor unit?

Stop using it. Mitsubishi Electric lists "When water leaks or drips from the indoor unit" among the cases where owners should "stop using the air conditioner and consult your dealer."

Gree's list says that if the indoor unit is leaking, owners should turn it off, disconnect the power immediately and call the dealer or a qualified professional.

MRCOOL's caution box includes water falling into or out of the unit, and says to turn it off at once and contact an authorized service provider.

Why is my mini split hissing?

A soft hiss from a mini split is refrigerant on the move, especially as the system starts, stops or changes direction for defrost. MRCOOL and Mitsubishi Electric both list hissing as normal.

MRCOOL separates two kinds. A "Low hissing sound during operation" comes from refrigerant gas flowing through the indoor and outdoor units. A low hiss as the system starts, just after it stops, or while defrosting comes from the gas "stopping or changing direction." Mitsubishi Electric says an occasional hiss "is the sound when the flow of refrigerant inside the unit is changed."

Why is my mini split making noise when off?

A mini split that sounds busy after you switch it off is usually finishing a job: draining, cooling down, preheating the outdoor unit or running a cleaning cycle. LG, Gree, MRCOOL and Pioneer each describe one of these.

LG's two-hourly preheat relay and its after-shutdown dripping are the commonest. Gree pins both its running water sound and its cracking to a unit "turned on or turned off just now," which places them in the minutes after you press OFF.

A cleaning cycle can also outlast the remote. MRCOOL's and Senville's Active Clean turns the unit off automatically when it finishes, and Pioneer's Self-Clean gives "Two beeps" when it ends. Some MRCOOL and Senville outdoor units also run their fan backwards for 70 seconds after shutdown to blow dust off the coil.

On a multi-zone system, an idle head can still hiss or trickle while another room calls for heat or cooling, because refrigerant keeps moving through the shared pipework. Our heat pump noise page quotes Mitsubishi Electric on this.

If the indoor fan starts on its own and the display shows a code, read the next section before anything else.

Why does my mini split beep or buzz?

A short beep or buzz from a mini split is usually confirmation that the head heard the remote or powered up normally. A buzzer that keeps sounding beside an error code can be a refrigerant leak alarm.

Pioneer says: "Each time the air conditioner is powered on, a buzzing sound indicates normal operation. If you do not hear this sound, the unit may be malfunctioning." MRCOOL and Senville print the same check. Pioneer adds that "The unit beeps to confirm each button command."

Mitsubishi Electric's heads give two short beeps when fan speed or vane direction is set to AUTO. When the remote sends a weekly timer, a long beep means the head got it and three short beeps mean it did not.

What does a long buzz with an error code mean?

On MRCOOL and Senville units with a refrigerant sensor, it may mean a leak.

MRCOOL says that when the sensor detects one, the head "will display an error code and emit a buzzing sound," the outdoor compressor stops "and the indoor fan will start running." For codes EHC1 and EHC2, MRCOOL says the buzzer "will continue to beep for 5 to 6 minutes before stopping."

MRCOOL's manual says the sensor "cannot be repaired" and can only be replaced by the manufacturer, and the caution box in its troubleshooting section tells owners: "DO NOT ATTEMPT TO FIX THESE YOURSELF!" Leave the unit powered, as the manual requires, and contact an authorized service provider or the dealer who installed it.

What does a mini split do indoors during defrost?

During defrost, a mini split's indoor head goes quiet: the fan stops, warm air pauses for a few minutes, and a display code or lamp shows the outdoor unit clearing frost, as Pioneer, Mitsubishi Electric, MRCOOL and Fujitsu describe.

Pioneer's manual says the defrost cycle "lasts between 2 and 10 minutes" and that "During defrosting, the indoor unit's fan will stop." Mitsubishi Electric's table answers a head that stops for about 10 minutes in heating with "Outdoor unit is in defrost," adding that it finishes "in max. 10 minutes, please wait."

The display is the quickest way to confirm it. MRCOOL lists "DF" as its defrost code. Fujitsu says "During Automatic Defrosting operation, the OPERATION indicator lamp will flash." Senville's display also shows a defrost indicator.

When heating resumes, MRCOOL says white mist from the head is moisture from the defrost and is normal. The whoosh and steam outside are covered in our heat pump noise explainer.

Why is the fan slow or silent when heating starts?

The head is waiting for its coil to warm up so it does not blow cold air.

Pioneer says the system "may take up to 10 minutes to deliver heat." Fujitsu says fan speed at the start of heating "is temporarily very low, to allow internal parts to warm up," and Gree describes a delay of several minutes as "a normal phenomenon."

Pioneer adds that in heating you cannot pick the fan speed; it rises and falls "in proportion to the temperature of the heat exchanger." So a head that gets louder, then quieter, through a winter evening is following its coil, not misbehaving.

Why is my mini split rattling or humming?

A rattle or tap from a mini split's indoor head can mean the fan is touching its housing, which LG says needs service. A hum that rises and falls is usually the outdoor compressor changing speed.

LG's wording is plain: "A loud rattling or tapping sound may occur if the indoor unit fan touches the unit housing." Its advice is to contact LG Customer Support, and more broadly, "Do not attempt to repair mechanical rattling sounds yourself."

Mitsubishi Electric's checks for a vane that will not move are whether the vanes are seated correctly and whether the fan guard is bent. Vibration through the wall is an installation matter. Pioneer tells installers to mount the head "with rubber gaskets to reduce vibration and noise," where allowed.

For humming, LG says the inverter compressor outside makes "a humming sound that gets louder or quieter as the speed adjusts."

Which mini split noises mean you should switch it off?

Loud or abnormal sounds are the trigger in every manual we read. MRCOOL, Gree and Mitsubishi Electric say to stop the unit and get service, and MRCOOL and Gree say not to repair it yourself.

MRCOOL's caution box begins "If any of the following conditions occur, turn off the unit immediately," and lists a damaged or warm wire, a burning odor, "loud or abnormal sounds," a fuse or breaker that keeps tripping, and water or objects falling into or out of the unit. It then tells owners to contact an authorized service provider straight away.

Gree's list is close: an overheating or damaged power cord, "abnormal sound during operation," a breaker that trips often, a burning smell, or a leaking indoor unit. Its instruction is to turn the unit off, disconnect power and contact the dealer, and it adds: "Do not repair or refit the air conditioner by yourself."

Mitsubishi Electric's version is shortest: when "an abnormal sound is heard," or any refrigerant leak is found, stop using it and consult your dealer. MRCOOL's and Senville's current heads use R-454B, which both manuals handle as a flammable refrigerant, so anything past the filter and the remote belongs to a technician.

How loud is a normal mini split indoor unit?

A wall-mounted head on its lowest fan speed lists roughly 17.5 to 30 dB(A) on maker spec sheets, rising to the mid 40s on its highest speed. Few makers say how they measured, so treat the figures as a guide.

Indoor ladders printed by four makers, as collected in our quietest mini-splits guide:

  • MRCOOL DIY Select 12k: 44.5, 40, 35, 25.5 and 17.5 dB(A), Turbo down to its silent speed
  • Mitsubishi Electric GX Premier MSZ-GX09NL: 19, 22, 30, 37 and 43 dB(A), Quiet up to Super High
  • Pioneer 12,000 BTU 115V system: 28 dB(A) on Mute, 45 on Turbo
  • Klimaire DIY 9k: 30 dB(A) at its quietest, measured in cooling

Fujitsu is the one maker in that guide that states its method, an anechoic chamber, and it warns that real installations can measure louder. Our Mitsubishi mini-split decibels page lists every M-Series head by fan speed.

Fan speed is the setting an owner controls. Pioneer's Mute runs the head "at its lowest fan speed in order to minimize operation noise," and Mitsubishi recommends a lower speed "for quiet operation." Our explainer on quiet and sleep modes covers what those settings trade away.

How do mini split makers measure indoor unit noise?

Most mini split makers do not say how they measured indoor unit noise. All 98 ductless systems in our catalog on October 26, 2026 print an indoor figure, and 22 name an anechoic chamber or room as the test space. The counts describe our catalog, not the whole ductless market.

Those 22 come from three makers: 10 Fujitsu systems, 6 Mitsubishi Electric and 6 Daikin. Our catalog records a microphone distance for 8 of them. Mitsubishi Electric's GX and FX manuals place it 1 m from the unit, and Daikin's engineering data puts it 1 m in front of and 0.8 m below a wall unit, or 1.5 m below its Vista cassette.

Mitsubishi Electric's note explains why a head can sound louder at home than on paper. The level is measured "when compressor stops", and "The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation." Fujitsu's submittals warn that installed units "might be higher than the specified values here."

Units, ranges and modes on the spec sheets

Senville's 17 systems print plain dB on senville.com, with no A-weighting, distance or mode named. Gree's 9 systems and the single DELLA system give only a minimum to maximum range, with no fan speed attached to either end.

Twenty-seven systems, every Mitsubishi Electric, Fujitsu and Daikin one, print separate cooling and heating rows, and the two can differ. Fujitsu's 24,000 BTU Altair 500 head reads 51 dB(A) on High in cooling and 47 in heating.

So MRCOOL's 17.5 dB(A) silent speed on the DIY Select 12k, with no test space named, and the 19 dB(A) Quiet speed of Fujitsu's 9,000 BTU Altair 500, taken in its own chamber, were not measured the same way. This page does not rank one above the other; each figure is best read against the same maker's other models.

How did we put this page together?

Seven maker documents supplied every sound here, all listed in the sources below.

They are Mitsubishi Electric's MSZ-GL operating instructions, Gree's Livo indoor owner's manual, MRCOOL's DIY 5th Gen manual, Pioneer's WYT20U manual, Senville's Leto manual, LG's US noise guide and Fujitsu's AIRSTAGE troubleshooting FAQ. The measurement counts come from the indoor noise lines of the 98 systems in our three mini-split catalog files, checked by hand on October 26, 2026.

Nobody at QuietSpecs installed, opened, cleaned or listened to a ductless head while writing this, and the drain hose and mounting advice above is untried by us. Where a maker explains a sound but offers no fix, we have left it that way rather than suggest one.

What makers publish

The noise figures makers print for models in our buying guides, word for word, with any setting or distance they give. Figures taken under different conditions are not comparable, so this list does not rank them.

The quietest mini-split heat pumps you can buy online

ModelNoise figure, as published
MRCOOL DIY 5th Generation Single Zone 12,000 BTU Ductless Mini-Split Heat Pump (115V)43 / 39.5 / 33.5 / 24 / 18 dB(A), Turbo to Si (maker)
MRCOOL DIY Hyper Heat Single Zone 12,000 BTU Ductless Mini-Split Heat Pump45.5 / 40 / 34 / 22.5 / 18 dB(A), Turbo to Si (maker)
Klimaire KIWQ-KOIQ DIY 5th Generation Series 9,000 BTU Do-It-Yourself Mini Split Heat Pump with E-Z Kuick Connect Installation Kit (115V)43 / 40 / 33 / 31 / 30 dB(A) in cooling, Turbo to Mute (maker)
MRCOOL DIY Select Single Zone 12,000 BTU Ductless Mini-Split Heat Pump44.5 / 40 / 35 / 25.5 / 17.5 dB(A), Turbo to Si (maker)
Pioneer Diamante Essenza 12,000 BTU 20 SEER2 115V High-Wall Ductless Mini-Split Air Conditioner Inverter Heat Pump with 16 Ft. Kit45 / 42 / 35 / 30 / 28 dB(A), Turbo to Mute (maker)

All 6 models in the guide

How loud is a Mitsubishi mini split? From 19 dB(A) on Quiet

ModelNoise figure, as published
Mitsubishi Electric M-Series MSZ-GX09NL and MUZ-GX09NL 9,000 BTU/H GX Premier Wall-Mounted System19 / 22 / 30 / 37 / 43 dB(A), Quiet to Super High, cooling (maker)
Mitsubishi Electric M-Series MSZ-FX09NL and MUZ-FX09NLHZ 9,000 BTU/H FX Deluxe Wall-Mounted Hyper-Heating System20 / 23 / 29 / 36 / 44 dB(A), Quiet to Super High, cooling (maker)
Mitsubishi Electric M-Series MSZ-HX09NL and MUZ-HX09NL 9,000 BTU/H HX Wall-Mounted System22 / 30 / 37 / 43 dB(A), Low to Super High, cooling (maker)
Mitsubishi Electric M-Series MSZ-JX09WL and MUZ-JX09WL 9,000 BTU/H JX 115V Wall-Mounted System22 / 30 / 37 / 43 dB(A), Low to Super High, cooling (maker)
Mitsubishi Electric M-Series MSZ-HX18NL and MUZ-HX18NL 18,000 BTU/H HX Wall-Mounted System30 / 37 / 42 / 47 dB(A), Low to Super High, cooling (maker)

All 7 models in the guide

Fujitsu mini split decibels start at 19 dB(A) on its Quiet speed

ModelNoise figure, as published
Fujitsu AIRSTAGE Altair 700 Series 9,000 BTU Wall Mounted System (ASUH09KMAS / AOUH09KMAS1)19 / 30 / 35 / 40 dB(A), Quiet / Low / Med / High, cooling (maker)
Fujitsu AIRSTAGE Altair 300 Series 9,000 BTU 115V Wall Mounted System (ASLH09KNAS / AOLH09KNAS1)20 / 27 / 35 / 41 dB(A), Quiet / Low / Med / High, cooling (maker)
Fujitsu AIRSTAGE Altair 500 Series 18,000 BTU Wall Mounted System (ASUH18KPAS / AOUH18KPAS1)26 / 37 / 40 / 42 / 43 / 44 dB(A), Quiet / Low / Med-Low / Med / Med-High / High, cooling (maker)
Fujitsu AIRSTAGE Orion XLTH Series 18,000 BTU Wall Mounted System (ASUH18KZAS / AOUH18KZAH1)30 / 33 / 36 / 39 / 42 / 44 dB(A), Quiet / Low / Med-Low / Med / Med-High / High, cooling (maker)
Fujitsu AIRSTAGE Orion XLTH Series 24,000 BTU Wall Mounted System (ASUH24KZAS / AOUH24KZAH1)30 / 33 / 36 / 39 / 42 / 44 dB(A), Quiet / Low / Med-Low / Med / Med-High / High, cooling (maker)

All 8 models in the guide

Senville mini split noise level chart, 21 to 34 dB on low

ModelNoise figure, as published
Senville LETO Series 9000 BTU Mini Split Air Conditioner and Heat Pump SENL-09CD (110V)36.5 / 31.0 / 22.0 dB, H / M / L (maker, no mode stated)
Senville LETO Series 12000 BTU Mini Split Air Conditioner and Heat Pump SENL-12CD/220 (220V)44.0 / 38.0 / 32.0 / 22.5 dB, Turbo / H / M / L (maker, no mode stated)
Senville ELITE Series 12000 BTU Mini Split Air Conditioner and Heat Pump SENE-12EL41.5 / 41.5 / 33 / 23 dB, Turbo / H / M / L (maker, no mode stated)
Senville AURA Series 15000 BTU Mini Split Air Conditioner and Heat Pump SENA-15HF58.5 / 36.5 / 32.5 / 21.0 / 18.0 dB, Turbo / H / M / L / Si (maker, no mode stated)
Senville LETO Series 18000 BTU Mini Split Air Conditioner and Heat Pump SENL-18CD50.5 / 45 / 36 / 24 dB, Turbo / H / M / L (maker, no mode stated)

All 8 models in the guide

Frequently asked questions

Why does my mini split make a clicking noise when it is off?

On LG wall-mounted units, a relay inside the indoor head can switch on roughly every two hours to preheat the outdoor unit, and LG calls the click or clunk normal. Gree and Mitsubishi Electric add panels that crack as they change temperature just after the unit stops. A click that repeats every few seconds is on no maker's list we read.

Why does my mini split gurgle when the kitchen fan is on?

Mitsubishi Electric explains it: switching on a range hood or ventilation fan draws outside air in through the drain hose, and the water in the hose spouts and burbles. Strong wind blowing into the hose end does the same. The manual lists it as a normal sound, not a fault.

Is it normal to hear water dripping in a mini split after turning it off?

Yes. LG describes a normal dripping sound from the indoor unit shortly after shutdown, often where a concealed drain hose bends, and says a longer hose can reduce it. Water you can see leaking from the head is different: Mitsubishi Electric, Gree and MRCOOL all say to stop using the unit and get service.

Why did my mini split stop blowing warm air for ten minutes?

The outdoor unit is almost certainly defrosting. Pioneer says the indoor fan stops for 2 to 10 minutes, Mitsubishi Electric says to wait because defrost finishes within 10 minutes, MRCOOL heads show DF and Fujitsu flashes the OPERATION lamp. Heating resumes on its own afterwards.

Why does my new mini split beep or buzz when the power comes on?

Pioneer, MRCOOL and Senville each say a buzz at power-on confirms the unit started normally, and that silence may point to a problem. A buzzer that keeps sounding with an error code is different: on MRCOOL units with a refrigerant sensor, it signals a detected leak.

Which mini split noises mean I should turn it off?

Loud or abnormal sounds during operation, according to MRCOOL, Gree and Mitsubishi Electric, along with a burning smell, a tripping breaker or water leaking from the head. MRCOOL and Gree also say to cut the power and not to repair the unit yourself, and LG says to call its support line for a fan that rattles against its housing.

How we reviewed this article

Every statement here comes from the 7 maker documents, standards and agency pages listed under Sources, quoted where the wording matters. We did not measure, inspect or repair anything ourselves. Each substantive revision is dated below. How we work

  1. Current version

    First published, written by Stanley Alu.

Sources

Every figure on this page was read on one of the pages below. We did not measure anything ourselves.

Written by

Stanley Alu

Founder and editor

I founded QuietSpecs after running a product review blog, and I built it around the spec that is hardest to pin down. With noise, makers tend to quote the quietest setting they can find, or nothing at all. So I read the spec sheets, manuals and certification directories, quote each figure with the setting it describes, and say so plainly when a maker publishes none. I do not test products or measure decibels, and no brand pays for a place in a guide.

How we compare products

Related buying guides

More in Why Is It Noisy